March 4, 2020 Water Retest Update

Early Childhood Center

Four outlets were tested, three were retested after they were flushed and aerated. The three outlets retested remain at elevated levels. All outlets that continue to test at or over the limit for either copper or lead will be kept offline until they can be repaired. All outlets will be retested before they are brought back into use.                                                                                                                                                                      

Room 121 (Water Fountain)(Bubbler)(lead):0.177 mg/L

Room 121 (Bathroom)(lead):0.222 mg/L

Room 121 (Sink 2)(lead):0.102 mg/L

The EPA action level for lead is 0.015 mg/L

The EPA action level for lead is 0.015 mg/L

Across from Room 121 (Water Bottle Filling Station) did not have elevated levels of lead or copper.

ECC retesting results report (PDF).