Summer Retesting of Winter 2020 Results

 Winter 2020 water test results that came back high were remediated and were retested prior to July 1, 2020. Due to COVID-19, testing for elevated results in the following two schools was not carried out by July 1, when the law for allowable lead levels in school drinking water changed from 15 parts per billion to 10 parts per billion. The actionable level for copper remains at 1.3 mg/L.

 

John Adams Elementary School

Of the 8 samples collected on 8/26/20; 5 outlets tested above the action level for lead and/or copper.

Room 152 Left Sink (Sink)(Lead): 0.021 mg/L
Room 152 Right Sink (Sink)(Lead): 0.023 mg/L
Room 153 (Sink)(Lead): 0.054 mg/L
Room 154 (Sink)(Copper): 2.660 mg/L (Lead): 0.555 mg/L - Copper and Lead elevated above at this Sink
Room 138 (Sink)(Lead): 0.765 mg/L

The fixtures in these 5 rooms will be replaced by October 2, 2020

 
Early Childhood Center

Of the 4 samples collected on 8/26/20; 4 outlets tested above the action level for lead.

Room 121 Left Sink Bubbler (Bubbler)(Lead): 0.454 mg/L
Room 121 Left Sink (Sink)(Lead): 0.658 mg/L
Room 121 Right Sink (Sink)(Lead): 0.026 mg/L
Room 121 Bathroom Sink (Sink) (Lead): 0.051 mg/L

The fixtures/units in these 4 rooms will be replaced by October 2, 2020

Once this work has been completed, the water will be retested and ACPS will collect follow-up samples to ensure it remains within safe limits in the future.

 

George Washington Middle School

The following outlets at George Washington Middle School were still elevated in July 2020.

Room A335 (Sink)(copper): 0.131 mg/L

Room A116 (Teacher’s desk sink)(lead): 0.024 mg/L

Room A335 (Sink)(lead): 51.200 mg/L

Given the change of allowable lead limits, the Office of Safety and Security conducted a review of previous water quality testing results at George Washington Middle School and at Douglas MacArthur on Taney Ave. to determine if there are any outlets that must now be deemed “elevated” and thus added to the remediation plan.  

Review of George Washington Middle School:

George Washington Middle School

The following outlets at George Washington Middle School are elevated since the new law was applied.

Of the 132 samples collected, the following 8 outlets tested above the actionable levels for copper and lead.

Lead results above the VA action level of 0.10 mg/L:

Room A136 (Sink 1)(lead): 0.012 mg/L

Room A136 (Sink 2)(lead): 0.014 mg/L

Room A239 (Sink)(lead): 0.013 mg/L

Room C201 (Sink)(lead): 0.010 mg/L

Room C203 (Sink)(lead): 0.010 mg/L

Room A344 (Sink)(lead): 0.011 mg/L

Room C111 (Sink 1)(lead): 0.010 mg/L

Room C111 (Sink 2)(lead): 0.013 mg/L

 

Douglas MacArthur on Taney Ave.

The following outlets at Douglas MacArthur on Taney Ave. are elevated since the new law was applied.

Of the 55 samples collected, 20 outlets tested above the actionable level for lead.

Lead results above the VA action level of 0.10 mg/L:

Hall (Water Fountain)(lead): 0.018 mg/L

Room 1002D (Sink)(lead): 0.013 mg/L

Room 1004A/B (Bubbler)(lead): 0.015 mg/L

Room 1006A/B (Bubbler)(lead): 0.029 mg/L

Room 1008A/B (Sink)(lead): 0.526 mg/L

Room 1010 (Bubbler)(lead): 0.017 mg/L

Room 1014 (Bubbler)(lead): 0.011 mg/L

Room 1119 (Bubbler)(lead): 0.015 mg/L

Room 1117 (Bubbler)(lead): 0.037 mg/L

Room 1115 (Sink)(lead): 0.011 mg/L

Room 1115 (Bubbler)(lead): 0.023 mg/L

Room 1113 (Bubbler)(lead): 0.029 mg/L

Room 1035E (Sink)(lead): 0.013 mg/L

Room 1055 (Bubbler)(lead): 0.021 mg/L

Room 1038 (Sink)(lead): 0.012 mg/L

Room 1034A (Right Sink)(lead): 0.010 mg/L

Room 1068 (Bubbler)(lead): 0.016 mg/L

Room 1070 (Sink)(lead):  0.012 mg/L

Room 1070 (Bubbler)(lead): 0.036 mg/L

Room 1075 (Right Sink)(lead): 0.045 mg/L